E2615-H2S

Hydrogen Sulfide Transmitter
E2615-H2S
Features
  • Maintenance free long-life sensor
  • User selectable output 4-20 mA / 0-10 V
  • Range of compact wall mount enclosures
  • Low cost for volume HVAC applications
Description

Hydrogen sulfide transmitter E2615-H2S is a new low cost device intended to use in HVAC applications. 

The device operates in the range of 0-50 ppm.

The transmitter is based on a miniature electrochemical sensor with long lifetime. The sensor requires no field recalibration during the whole lifespan.

The analog output of the device is user settable to 4-20 mA or 0-10 V.

The device is available either in a slotted IP20 enclosure or in a IP65 enclosure.


Technical Data
Detected gas Hydrogen Sulfide
Sensor type Electrochemical
Sampling method Diffusion
Detection range 0-50 ppm
Sensor lifetime > 2 years
Power supply 24 VDC ± 20%
Analog output 4-20 mA / 0-10 V, user settable
Enclosure ABS plastic with ventilation slots,
wall mount, protection class IP20
or ABS plastic, wall mount, protection class IP65
Dimensions H71 × W71 × D27 mm (IP20 version)
H70 × W52 × D36 mm (IP65 version)
Operating conditions -30...+50 °C
-20 to 40 °C continuous recommended
15-95% RH constantly
0...100% RH intermittently
atmospheric pressure ±10%
for IP20 version non-condensing


Similar Products


E2608-H2S - Hydrogen Sulfide Detector
E2608-H2S - Hydrogen Sulfide Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 or 0...2000 ppm H2S
  • Resolution 0,1 ppm or 1 ppm H2S
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-H2S - Hydrogen Sulfide Transmitter
E2618-H2S - Hydrogen Sulfide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...100 or 0...2000 ppm H2S
  • Resolution 0,1 ppm or 1 ppm H2S
  • 2 × 4-20 mA or 0-10 V, RS485

E2638-H2S - Hydrogen Sulfide Detector
E2638-H2S - Hydrogen Sulfide Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 or 0...2000 ppm H2S
  • Resolution 0,1 ppm or 1 ppm H2S
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2648-H2S - Hydrogen Sulfide Detector
E2648-H2S - Hydrogen Sulfide Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 or 0...2000 ppm H2S
  • Resolution 0,1 ppm or 1 ppm H2S
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485