E2608-NH3-P

Ammonia Detector
E2608-NH3-P
Features
  • Stable long-life pellistor gas sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485
  • Wall-mount or duct-mount version
  • Attached or remote sensor
Description

Ammonia detector-transmitter E2608-NH3-P is a member of the PluraSens® family of multifunctional measurement instruments.

One of the most common applications is detection of explosive Ammonia concentrations in refrigeration machinery rooms.

The instrument utilizes a fully calibrated and temperature compensated pellistor (catalytic) gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact may be used for remote signaling or ventilation control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical Data
Calibration Ammonia NH3
Sensor type Pellistor (catalytic bead)
Sampling method Diffusion
Detection range 0...15%vol. (0…100%LEL NH3)
Resolution 0.1%vol. or 1%LEL
Response time T90 ≤10 s
Sensor lifetime > 3 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Enclosure grey ABS plastic, wall mount, IP65
Dimensions H85 × W82 × D55 mm
Operating conditions -10...+50 °C, 0...95% RH