- Stable long-life electrochemical sensor
- Range 0...300 or 0...1000 ppm CO
- Resolution 1 ppm CO
- Two SPST relays
- 2 × 4-20 mA or 0-10 V, RS485
Carbon monoxide detector-transmitter E2608-CO is a member of new PluraSens® family of multifunctional measurement instruments.
Applications include underground parkings, boiler houses, kitchens, and other confined spaces, where potentially toxic concentration of carbon monoxide can accumulate.
The instrument utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.
Two relays with closing contact may be used for remote signalling or ventilation control. Two alarm set-points are user settable.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Calibration | carbon monoxide CO |
Sensor type | electrochemical |
Sampling method | diffusion |
Detection range | 0...300 ppm CO |
0...1000 ppm CO | |
Resolution | 1 ppm CO |
Sensor lifetime | > 10 years |
Power supply | 12...36 VDC (default), |
24 VAC or 230 VAC as options | |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays | 2 × SPST relays (closing contact), |
250 VAC / 30 VDC, 5 A max | |
Default alarm set-points | 25 ppm / 35 ppm CO |
Enclosure | grey ABS plastic, wall mount, IP65 |
Dimensions | H85 × W82 × D55 mm |
Operating conditions | -20...+50 °C, 15...90 %RH |