- Stable long-life metal-oxide sensor
- Ranges 0...1000 / 0...2500 ppm halocarbon gas
- Resolution 1 ppm halocarbon gas
- Two SPST relays
- 2 × 4-20 mA or 0-10 V, RS485
Refrigerants detector-transmitter E2611-HFC is a member of new PluraSens® family of multifunctional measurement instruments.
Applications include cold storage warehouses, skating arenas, and other areas, where leakages of halocarbon refrigerants are possible.
The instrument utilises a fully calibrated metal-oxide semiconductor gas sensor with excellent repeatability, stability and long lifetime. The sensor is highly sensitive to a wide range of CFC, HFC and HFO compounds, including R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R-507, R-514a, R-1234yf, R-1234ze and similar.
Two relays with closing contact may be used for remote signalling or ventilation control. Two alarm set-points are user settable. Internal buzzer gives sound alarms.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Detected gases | R-12, R-123, R-125, R-134a, R-143, R-22, R-404a, R-407c, R-410a, R-507, R-514a, R-1234yf, R-1234ze etc |
Default calibration | R-404a |
Sensing method | metal-oxide semiconductor |
Sampling method | diffusion |
Detection ranges | 0...1000 ppm halocarbon gas |
0...2500 ppm halocarbon gas | |
Resolution | 1 ppm halocarbon gas |
Sensor lifetime | >5 years |
Power supply | 12...36 VDC (default), |
24 VAC or 230 VAC as options | |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays | 2 × SPST relays (closing contact), |
250 VAC / 30 VDC, 5 A max | |
Alarms | buzzer 85 dB |
Alarm setpoints | minimum 250 ppm |
Enclosure | light-grey ABS plastic with ventilation slots, IP20 |
Dimensions | H85 × W85 × D37 mm |
Operating conditions | -30...+60 °C, 0...95 %RH |