E2670-NO2

Flameproof Nitrogen Dioxide Detector
E2670-NO2
Features
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
Description

E2670 series is a new line of flameproof detectors-transmitters intended for use in ATEX Zones 2 and 22.

E2670 series devices are based on PluraSens® multifunctional platform.

Nitrogen dioxide detector-transmitter E2670-NO2 utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical Data
Calibration nitrogen dioxide NO2
Sensor type electrochemical
Sampling method diffusion
Detection range 0...20 ppm NO2
0...200 ppm NO2
Resolution 0,1 ppm NO2 for 20 ppm range
1 ppm NO2 for 200 ppm range
Sensor lifetime > 2 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Default alarm set-points 3 ppm / 6 ppm NO2
Enclosure die-cast aluminium, wall mount, IP65
Dimensions H155 × W145 × D110 mm
Operating conditions -20...+50 °C, 15...90 %RH
safe areas and ATEX Zones 2 and 22


Similar Products


E2608-NO2 - Nitrogen Dioxide Detector
E2608-NO2 - Nitrogen Dioxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-NO2 - Nitrogen Dioxide Transmitter
E2618-NO2 - Nitrogen Dioxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • 2 × 4-20 mA or 0-10 V, RS485

E2630-NO2 - Nitrogen Dioxide Detector
E2630-NO2 - Nitrogen Dioxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...10 ppm NO2
  • Resolution 0,1 ppm NO2
  • Two SPST relays
  • UART digital interface

E2660-CO-NO2 - Carbon Monoxide-Nitrogen Dioxide Transmitter
E2660-CO-NO2 - Carbon Monoxide-Nitrogen Dioxide Transmitter
  • Simultaneous CO and NO2 monitoring
  • RS485 Modbus RTU digital interface
  • Two analog outputs 4-20 mA / 0-10 V
  • Easy-to-install IP65 protected enclosure
  • Attached or remote sensor
  • Two SPST relays option
  • Acoustic alarm option