- High long-term stability
- User selectable output 4-20 mA / 0-10 V
- Range of compact wall mount enclosures
- Low cost for volume HVAC applications
Nitrogen dioxide transmitter E2615-NO2 is a new low cost device intended to use in HVAC applications.
The device operates in the range of 0-30 ppm.
The transmitter is based on a miniature electrochemical sensor with long lifetime (> 2 years). The sensor requires no field recalibration during the whole lifespan.
The analog output of the device is user settable to 4-20 mA or 0-10 V.
The device is available either in a slotted IP20 enclosure or in a IP65 enclosure.
Detected gas | Nitrogen Dioxide |
Sensor type | Electrochemical |
Sampling method | Diffusion |
Detection range | 0-30 ppm |
Sensor lifetime | ≥ 2 years |
Power supply | 24 VDC ± 20% |
Analog output | 4-20 mA / 0-10 V, user settable |
Enclosure | ABS plastic with ventilation slots, wall mount, protection class IP20 |
or ABS plastic, wall mount, protection class IP65 | |
Dimensions | H71 × W71 × D27 mm (IP20 version) |
H70 × W80 × D36 mm (IP65 version) | |
Operating conditions | -20...+50 °C |
15...90 %RH, | |
pressure 0,9...1,1 atm | |
for IP20 version non-condensing |