- Highly sensitive Photo Ionization Detector
- Range 0...40 or 0...200 ppm isobutylene
- Resolution 0,01 ppm or 1 ppm isobutylene
- 2 × 4-20 mA or 0-10 V, RS485
Volatile Organic Compounds transmitter E2618-PID is a member of new PluraSens® family of multifunctional measurement instruments.
The instrument utilises highly sensitive photoionization detectors (PID) with extremely low minimal detection levels. The transmitter exhibits sensitivity to compounds with ionization potential less than 10.6 eV, i.e. to most solvent vapors.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the transmitter to safety or building automation systems.
Detected vapors | acetone, ethanol, toluene, xylene etc |
Default calibration | isobutylene |
Sensor type | Photo Ionization Detector |
Sampling method | diffusion |
Detection range | 0...40 ppm isobutylene |
0...200 ppm isobutylene | |
Resolution | 0,01 ppm C4H8 for 40 ppm range |
1 ppm C4H8 for 200 ppm range | |
Sensor lifetime | 5 years |
Power supply | 12...36 VDC (default) |
24 VAC as option | |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Enclosure | grey ABS plastic, wall mount, IP65 |
Dimensions | H82 × W80 × D55 mm |
Operating conditions | -40...+65 °C, < 95 %RH |