E2618-LEL

Combustible Gas Transmitter
E2618-LEL
Features
  • Stable long-life metal-oxide / pellistor gas sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Wall mount or duct mount version
  • Attached or remote sensor
  • 2 × 4-20 mA or 0-10 V, RS485
Description

Combustible gas detector E2618-LEL is a member of PluraSens® family of multifunctional measurement instruments. The device exhibits sensitivity to hydrogen, methane, acetylene, propane and butane

Applications include underground parkings, boiler houses, battery charging rooms, kitchens, and other confined spaces, where potentially explosive concentration of combustible gases can accumulate.

The instrument utilises fully calibrated metal-oxide semiconductor or pellistor gas sensors with excellent repeatability, stability and long lifetime.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the transmitter to safety or building automation systems.


Technical Data
Detected gases hydrogen, methane, acetylene, propane, butane
Default calibration methane CH4
Sensor type metal-oxide semiconductor (MOS)
pellistor (catalytic bead) on demand
Sampling Diffusion
Detection range 0...100% LEL
Resolution 0,1 / 1 % LEL
Sensor lifetime >5 years (MOS)
>3 years (pellistor)
Power supply 12...36 VDC (default)
24 VAC as option
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Enclosure grey ABS plastic, IP65
Dimensions H82 × W80 × D55 mm
Operating conditions 0...95 %RH,
-40...+70 °C (MOS)
-10...+50 °C (pellistor)


Similar Products


E2618-CO - Carbon Monoxide Transmitter
E2618-CO - Carbon Monoxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...300 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-HFC - Refrigerant Transmitter
E2618-HFC - Refrigerant Transmitter
  • Stable long-life metal-oxide sensor
  • Ranges 0...1000 / 0...2500 ppm halocarbon gas
  • Resolution 1 ppm halocarbon gas
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-NH3-E - Ammonia Transmitter
E2618-NH3-E - Ammonia Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-CH4 - Methane Transmitter
E2618-CH4 - Methane Transmitter
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-H2S - Hydrogen Sulfide Transmitter
E2618-H2S - Hydrogen Sulfide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...100 or 0...2000 ppm H2S
  • Resolution 1 ppm H2S
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-NO2 - Nitrogen Dioxide Transmitter
E2618-NO2 - Nitrogen Dioxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-VOC - Solvent Vapors Transmitter
E2618-VOC - Solvent Vapors Transmitter
  • Stable long-life metal-oxide sensor
  • Range 0...100% LEL or 0...1000 ppm
  • Resolution 0,1% LEL or 1 ppm
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-O3 - Ozone Transmitter
E2618-O3 - Ozone Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...5 ppm or 0...1 ppm O3
  • Resolution 0,01 ppm O3
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-C2H4 - Ethylene Transmitter
E2618-C2H4 - Ethylene Transmitter
  • Humidity compensated electrochemical sensor
  • Range 0...10 / 0...200 / 0...1500 ppm C2H4
  • Resolution 0,1 / 1 / 1 ppm C2H4
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-SO2 - Sulfur dioxide Transmitter
E2618-SO2 - Sulfur dioxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...50 or 0...2000 ppm SO2
  • Resolution 0,1 ppm or 1 ppm SO2
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-CL2 - Chlorine Transmitter
E2618-CL2 - Chlorine Transmitter
  • Stable long-life electochemical sensor
  • Range 0...10 ppm Cl2
  • Resoluton 0,1 ppm Cl2
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-ETO - Ethylene Oxide Transmitter
E2618-ETO - Ethylene Oxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...100 ppm C2H4O
  • Resolution 0,1 ppm or 1 ppm C2H4O
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-NO - Nitric Oxide Transmitter
E2618-NO - Nitric Oxide Transmitter
  • Stable long-life electrochemical sensor
  • Detection range 0...250 ppm NO
  • Resolution 1 ppm NO
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-PID - Solvent Vapors Transmitter
E2618-PID - Solvent Vapors Transmitter
  • Highly sensitive Photo Ionization Detector
  • Range 0...40 or 0...200 ppm isobutylene
  • Resolution 0,01 ppm or 1 ppm isobutylene
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-CO2 - Carbon Dioxide Transmitter
E2618-CO2 - Carbon Dioxide Transmitter
  • Stable long-life photoacoustic or optical NDIR sensor
  • Range 0...10 000 ppm / 40 000 ppm / 5 %vol CO2
  • Resolution 1 ppm / 10 ppm / 0.01 %vol CO2
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-O2 - Oxygen Transmitter
E2618-O2 - Oxygen Transmitter
  • Electrochemical sensor
  • Range 0...25 %vol O2
  • Resolution 0,01 %vol O2
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-NH3-P - Ammonia Detector
E2618-NH3-P - Ammonia Detector
  • Stable long-life pellistor gas sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Wall mount or duct mount version
  • Attached or remote sensor
  • 2 × 4-20 mA or 0-10 V, RS485