E2615-CO

Carbon Monoxide Transmitter
E2615-CO
Features
  • High long-term stability
  • User selectable output 4-20 mA / 0-10 V
  • Range of compact wall mount enclosures
  • Low cost for volume HVAC applications
Description

Carbon monoxide transmitter E2615-CO is a new low cost device intended to use in HVAC applications. 

The device operates in the range of 0-300 ppm.

The transmitter is based on a miniature electrochemical sensor with long lifetime (≥ 7 years). The sensor requires no field recalibration during the whole lifespan.

The analog output of the device is user settable to 4-20 mA or 0-10 V.

The device is available either in a slotted IP20 enclosure or in a IP65 enclosure.


Technical Data
Detected gas Carbon monoxide
Sensor type Electrochemical
Sampling method Diffusion
Detection range 0-300 ppm
Sensor lifetime ≥ 7 years
Power supply 24 VDC ± 20%
Analog output 4-20 mA / 0-10 V, user settable
Enclosure ABS plastic with ventilation slots, wall mount, protection class IP20
or ABS plastic, wall mount, protection class IP65
Dimensions H71 × W71 × D27 mm (IP20 version)
H70 × W80 × D36 mm (IP65 version)
Operating conditions -20…+50 °C,
15-90 % RH,
pressure 0,9...1,1 atm
for IP20 version non-condensing


Similar Products


E2610-CO - Carbon Monoxide detector
E2610-CO - Carbon Monoxide detector
  • Stable long-life electrochemical sensor
  • Range 0...200 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Two SPDT relays
  • UART digital interface

E2608-CO - Carbon Monoxide Detector
E2608-CO - Carbon Monoxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...300 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-CO - Carbon Monoxide Transmitter
E2618-CO - Carbon Monoxide Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...300 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • 2 × 4-20 mA or 0-10 V, RS485

E2630-CO - Carbon Monoxide Detector
E2630-CO - Carbon Monoxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...200 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Two SPDT relays
  • UART digital interface

E2660-CO-NO2 - Carbon Monoxide-Nitrogen Dioxide Transmitter
E2660-CO-NO2 - Carbon Monoxide-Nitrogen Dioxide Transmitter
  • Simultaneous CO and NO2 monitoring
  • RS485 Modbus RTU digital interface
  • Two analog outputs 4-20 mA / 0-10 V
  • Easy-to-install IP65 protected enclosure
  • Attached or remote sensor
  • Two SPST relays option
  • Acoustic alarm option

E2638-CO - Carbon Monoxide Detector
E2638-CO - Carbon Monoxide Detector
  • Long-life electrochemical cell
  • Ranges 0...300 / 0...1000 ppm CO
  • Resolution 1 ppm CO
  • 4-20 mA / 0-10 V, RS485
  • Remote probe option
  • LCD option

E2660-CO-CO2 - Carbon Monoxide-Carbon Dioxide Transmitter
E2660-CO-CO2 - Carbon Monoxide-Carbon Dioxide Transmitter
  • Simultaneous CO and CO2 monitoring
  • RS485 Modbus RTU digital interface
  • Two analog outputs 4-20 mA / 0-10 V
  • Easy-to-install IP65 protected enclosure
  • Attached or remote sensor
  • Two SPST relays option
  • Acoustic alarm option

E2648-CO - Carbon Monoxide Detector
E2648-CO - Carbon Monoxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...300 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2660-CO-NO - Carbon Monoxide-Nitric Oxide Transmitter
E2660-CO-NO - Carbon Monoxide-Nitric Oxide Transmitter
  • Simultaneous CO and NO monitoring
  • RS485 Modbus RTU digital interface
  • Two analog outputs 4-20 mA / 0-10 V
  • Easy-to-install IP65 protected enclosure
  • Attached or remote sensor
  • Two SPST relays option
  • Acoustic alarm option

E2632-CO-CH4 - Two Channel Gas Detectors
E2632-CO-CH4 - Two Channel Gas Detectors
  • Simultaneous detection of two gases
  • Accurate and stable measurement
  • Wall-mount IP65 protected housing
  • Visual and acoustic alarms
  • Two output relays for alarm / ventilation control

E2670-CO - Flameproof Carbon Monoxide Detector
E2670-CO - Flameproof Carbon Monoxide Detector
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range 0...300 or 0...1000 ppm CO
  • Resolution 1 ppm CO
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485