- Suitable for ATEX Zones 2 and 22
- Stable long-life photoacoustic or optical NDIR sensor
- Range 0...10 000 ppm / 40 000 ppm / 5 %vol CO2
- Resolution 1 ppm / 10 ppm / 0.01 %vol CO2
- Two SPST relays (option)
- 2 × 4-20 mA or 0-10 V, RS485
E2670 series is a new line of flameproof detectors-transmitters intended for use in ATEX Zones 2 and 22.
E2670 series devices are based on PluraSens® multifunctional platform.
Carbon dioxide transmitter E2670-CO2 utilises a fully calibrated and temperature compensated photoacoustic gas sensor with excellent repeatability, stability and long lifetime. Ambient pressure compensation (in the range 0,5...2 bar of absolute pressure) is available as an option.
Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Calibration | carbon dioxide CO2 |
Sensor type | photoacoustic |
optical NDIR | |
Sampling method | diffusion |
Detection range | 0...10 000 ppm (10K) CO2 |
0...40 000 ppm (40K) CO2 | |
0...5 %vol (50KN) CO2 | |
up to 100 %vol CO2 on request | |
Resolution | 1 ppm for 10K |
10 ppm for 40K | |
0.01%vol for 50KN | |
Sensor lifetime | up to 10 years for 10K/40K |
up to 5 years for 50KN | |
Power supply | 12...36 VDC (default), |
24 VAC or 230 VAC as options | |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays (option) | 2 × SPST relays (closing contact), |
Enclosure | die-cast aluminium, wall mount, IP65 |
Dimensions | H155 × W145 × D110 mm |
Operating conditions | -40...+60 °C, 0...100 %RH |
safe areas and ATEX Zones 2 and 22 |