- Suitable for ATEX Zones 2 and 22
- Stable long-life electrochemical sensor
- Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
- Resolution 1 ppm NH3
- Two SPST relays option
- 2 × 4-20 mA or 0-10 V, RS485
E2670 series is a new line of flameproof detectors and transmitters intended for use in ATEX Zones 2 and 22.
E2670 series devices are based on PluraSens® multifunctional platform.
Ammonia detector-transmitter E2670-NH3-E a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.
Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.
Calibration | ammonia NH3 |
Sensor type | electrochemical |
Sampling method | diffusion |
Detection range | 0...100 ppm NH3 |
0...300 ppm NH3 | |
0...1000 ppm NH3 | |
0...5 000 ppm NH3 | |
up to 10000 ppm on request | |
Resolution | 1 ppm NH3 |
Sensor lifetime | > 2 years |
Power supply | 12...36 VDC (default), |
24 VAC or 230 VAC as options | |
Digital interface | RS485, Modbus RTU protocol |
Analog outputs | 2 × 4-20 mA / 0-10 V, user settable |
Output relays (option) | 2 × SPST relays (closing contact), |
250 VAC / 30 VDC, 5 A max | |
Default alarm set-points | 25 ppm / 35 ppm NH3 |
Enclosure | die-cast aluminium, wall mount, IP65 |
Dimensions | H155 × W145 × D110 mm |
Operating conditions | -40...+50 °C, -30...+50°C (for 0...5 000 ppm), |
15...90 %RH, | |
safe areas and ATEX Zones 2 and 22 |