- Wall mounting or ventilation airducts mounting (as option)
- Relative humidity, ambient temperature measurement
- Industrial IP65 protected enclosure
- Two configurable 0-10 V / 4-20 mA outputs
E2244 features 4 analog outputs 2x4-20 mA and 2x0-10 V for connection to various secondary instruments and controllers, BMS systems.
Possibility of having readings of relative humidity and ambient temperature at the same time.
Easy-to-install enclosure saves time on integration.
Measurement ranges | Wall-mount version 0…100 %RH, -40…+60 °C |
Duct-mount version 0…100 %RH, -40…+80 °C | |
Analog outputs | 4 analog outputs (2 x 0-10 V and 2 x 4-20 mA), programmable |
Resolution | 0,01 %RH / 0,01 °C |
Accuracy | ±2,5 % RH / ±0,5 °C |
±1,8 % RH / ±0,5 °C on request | |
Power supply | 12…30 VDC (24 VDC nominal) |
Operating conditions | -40...+60 °C, 0...100 %RH (non-condensing) |
Electromagnetic compatibility (CE marking) | according to 89-336-EEC and EN61326-1 requirements |