E2408-DP

Differential pressure transmitter-regulator
E2408-DP
Features
  • Ranges from -1000...+1000 Pa to -10...+10 kPa
  • 2 x 4-20 mA / 0-10 V outputs
  • Excellent repeatability and zero stability
  • Two analog outputs 4-20 mA or 0-10 V
  • Two configurable SPST output relays
  • RS485 Modbus RTU interface
Description

Differential pressure transmitter E2408-DP is a member of new PluraSens® family of multifunctional measurement instruments. The transmitter is intended for measurement of low pressure of air and non-aggressive gases in HVAC applications.

RS485 Modbus RTU interface allows direct Fieldbus networking of the devices and optional analog output can be used to connect the transmitter with additional secondary instruments.


Technical Data
Versions and max measurement ranges E2408-DP-1K -1000...+1000 Pa
E2408-DP-10K -10...+10 kPa
Analog outputs 2 × 3-wire 0-10 V or 4-20 mA, selectable
Relay outputs 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Output scales 0 - 250 Pa, -250…+250 Pa,
0 - 500 Pa, -500…+500 Pa,
0 - 1,0 kPa, -1,0…+1,0 kPa,
0 - 2,5 kPa, -2,5…+2,5 kPa,
0 - 5,0 kPa, -5,0…+5,0 kPa,
0 - 10 kPa, -10…+10 kPa
Resolution 0,1 / 10 Pa
Protection class IP65
Operating conditions -5...+65 °C, <95 %RH


Similar Products


E2408-DF - Differential pressure transmitter-regulator
E2408-DF - Differential pressure transmitter-regulator
  • Ranges from -50...+50 Pa to -500...+500 Pa
  • Calibrated and temperature compensated
  • 2 x 4-20 mA or 0-10 V analog outputs
  • Two configurable SPST output relays
  • RS485 Modbus RTU digital interface

E2418-DP - Differential pressure transmitter
E2418-DP - Differential pressure transmitter
  • Ranges from -1000...+1000 Pa to -10...+10 kPa
  • Calibrated and temperature compensated
  • 2 x 4-20 mA or 0-10 V analog outputs
  • RS485 Modbus RTU digital interface

E2407 - Barometric pressure transmitter
E2407 - Barometric pressure transmitter
  • Combined pressure and temperature sensor
  • Excellent repeatability and stability
  • Fully calibrated and temperature compensated
  • 2 x 4-20 mA or 0-10 V analog outputs
  • RS485 Modbus RTU digital interface

E2418-DF - Differential pressure transmitter
E2418-DF - Differential pressure transmitter
  • Ranges from -50...+50 Pa to -500...+500 Pa
  • Calibrated and temperature compensated
  • 2 x 4-20 mA or 0-10 V analog outputs
  • RS485 Modbus RTU digital interface