E2615-LEL

Combustible Gas Transmitter
E2615-LEL
Features
  • High long-term stability
  • User selectable output 4-20 mA / 0-10 V
  • Range of compact wall mount enclosures
  • Low cost for volume HVAC applications
Description

Combustible gases transmitter E2615-LEL is a new low cost device intended to use in HVAC applications. 

The device operates in the range of 0-100 % LEL.

The transmitter is based on a miniature pellistor sensor with long lifetime (> 3 years). The sensor requires no field recalibration during the whole lifespan.

The analog output of the device is user settable to 4-20 mA or 0-10 V.

The device is available either in a slotted IP20 enclosure or in a IP65 enclosure.


Technical Data
Calibration methane, propane, butane, hydrogen
Sensor type сatalytic bead (pellistor)
Sampling method diffusion
Detection range 0-100% LEL
Sensor lifetime > 3 years
Power supply 24 VDC ± 20%
Analog output 4-20 mA / 0-10 V, user settable
Enclosure ABS plastic with ventilation slots, wall mount, protection class IP20;
or ABS plastic, wall mount, protection class IP65
Dimensions H71 × W71 × D27 mm (IP20 version)
H70 × W80 × D36 mm (IP65 version)
Operating conditions -10....+50 °C,
0...95% RH
pressure 0,9...1,1 atm
for IP20 version non-condensing


Similar Products


E2611-CH4 - Methane Detector
E2611-CH4 - Methane Detector
  • Stable long-life metal-oxide sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1% LEL CH4
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2610-LEL - Combustible Gas Detector
E2610-LEL - Combustible Gas Detector
  • Stable long-life metal-oxide sensor
  • Range 0...100% LEL
  • Two SPDT relays
  • UART digital interface

E2608-CH4 - Methane Detector
E2608-CH4 - Methane Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2608-LEL - Combustible Gas Detector
E2608-LEL - Combustible Gas Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-CH4 - Methane Transmitter
E2618-CH4 - Methane Transmitter
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • 2 × 4-20 mA or 0-10 V, RS485

E2618-LEL - Combustible Gas Transmitter
E2618-LEL - Combustible Gas Transmitter
  • Stable long-life metal-oxide / pellistor gas sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Wall mount or duct mount version
  • Attached or remote sensor
  • 2 × 4-20 mA or 0-10 V, RS485

E2630-LEL - Combustible Gas Detector
E2630-LEL - Combustible Gas Detector
  • Stable long-life metal-oxide sensor
  • Range 0...100% LEL
  • Two SPDT relays
  • UART digital interface

E2638-CH4 - Methane Detector
E2638-CH4 - Methane Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2638-LEL - Combustible Gas Detector
E2638-LEL - Combustible Gas Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2611-LEL - Combustible Gases Detector
E2611-LEL - Combustible Gases Detector
  • Stable long-life metal-oxide sensor
  • Range 0...100% LEL
  • Resolution 0,1% LEL
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

E2648-CH4 - Methane Detector
E2648-CH4 - Methane Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2648-LEL - Combustible Gas Detector
E2648-LEL - Combustible Gas Detector
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2632-CO-CH4 - Two Channel Gas Detectors
E2632-CO-CH4 - Two Channel Gas Detectors
  • Simultaneous detection of two gases
  • Accurate and stable measurement
  • Wall-mount IP65 protected housing
  • Visual and acoustic alarms
  • Two output relays for alarm / ventilation control

E2670-CH4 - Flameproof Methane Detector
E2670-CH4 - Flameproof Methane Detector
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL CH4
  • Resolution 0,1 / 1 % LEL CH4
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2670-LEL - Flameproof Combustible Gas Detector
E2670-LEL - Flameproof Combustible Gas Detector
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life metal-oxide / pellistor sensor
  • Range 0...100% LEL
  • Resolution 0,1 / 1 % LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2660-CO-LEL - Combustible Gases Transmitter
E2660-CO-LEL - Combustible Gases Transmitter
  • Simultaneous CO and combustible gases monitoring
  • RS485 Modbus RTU digital interface
  • Two analog outputs 4-20 mA / 0-10 V
  • Easy-to-install IP65 protected enclosure
  • Attached or remote sensor
  • Two SPST relays option
  • Acoustic alarm option